5.1.3 Powering On Loads
Context
After the inverter starts, the UPS works in normal mode. The
Bypass mode
alarm disappears.
Procedure
Step 1
After confirming that the battery strings are properly connected, close the battery string input
circuit breaker. If there are multiple battery strings, close the circuit breaker for each battery
string and then the general circuit breaker between battery strings and the UPS. The
No
battery
alarm disappears from the MDU.
Step 2
Close the UPS downstream output switch to supply power to the loads.
----End
5.1.4 (Optional) Setting Parameters for the BCB Box
Prerequisites
A BCB box is installed.
Procedure
Step 1
On the
Settings
>
Dry Contact Set
screen, set
MUE05A connection
to
Enable
, and set
BCB
connection [OL]
and
Battery breaker [STA]
to
Enable
.