UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
C Alarm List
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
212
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
0088-1
Rack address
conflict
Critical
The configured rack
address conflicts
with another one.
Check the rack address setting.
0089-1
Rack output
overload
Minor
The load is
excessive.
The rack
capacity setting
is not
appropriate.
Check the load and remove
some loads or expand the UPS
power capacity if the UPS is
overloaded.
Check that the configured rack
capacity meets requirements.
0090-1
Dry contact board
fault
Critical
I2C communication
with the dry contact
board MUE05A
fails.
Replace the dry contact board
MUE05A.
0090-2
I2C communication
with the dry contact
board MUE06A
fails.
Replace the dry contact board
MUE06A.
0356
Battery Mode
Minor
The UPS is working
in battery mode.
The running status is displayed.
See details about how to handle
other alarms.
0359
No power supplied
Warning
No power is
supplied.
The running status is displayed.
See details about how to handle
other alarms.
0332
Output disabled
Minor
The output is
disabled.
The running status is displayed.
See details about how to handle
other alarms.
0337
PDC bypass input
breaker open
Critical
The bypass input
circuit breaker on
the PDC is OFF.
The running status is displayed.
No further measures are required.
0338
PDC output breaker
open
Critical
The output circuit
breaker on the PDC
is OFF.
1.
Check that all UPS output
circuit breakers are ON.
2.
On the LCD, check that
PDC
output breaker open
alarm
has disappeared. If the alarm
persists, tap the
Clear Fault
button to clear the alarm.
0341
PDC Maint. breaker
closed
Minor
The maintenance
circuit breaker on
the PDC is ON.
The running status is displayed.
No further measures are required.
0342
Mains input breaker
open
Critical
The mains input
circuit breaker is
OFF.
The running status is displayed.
No further measures are required.