UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
3 Installation
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
98
Table 3-5
Installation checklist
No.
Item
Acceptance Criteria
01
UPS installation
The UPS is securely installed and does not tilt
due to vibration.
02
Neat arrangement
The UPS and its adjacent cabinets are neatly
arranged and secured with connecting plates.
03
Cable layout
Cables are routed properly and cable routing
meets customer requirements.
04
Cable labels
Both ends of a cable are labeled. Labels are
concise and easy to understand.
05
Cable ties
Distances between cable ties are the same, and
no burr exists.
06
Cable connections
The input, output, and battery cables are
securely connected. For the cables secured by
screws, the washers are flattened.
07
Grounding
The resistance between the UPS ground bar
and the equipment room ground bar is less than
0.1 ohm.
08
AC phase sequence
For a single UPS, the mains input, bypass
input, and output phase sequences are correct.
For a parallel system, the phase sequences of
each UPS are consistent.
09
Battery cables
The battery strings are correctly connected to
the UPS.
10
Operating environment
The inside and outside of the cabinet, and other
operating components, are free from
conductive dust and foreign matter.
1.
Ensure that there is no foreign matter (such
as copper wires and screws) on the top of
the cabinet.
2.
Ensure that there is no foreign matter at the
copper bar terminals.
3.
Ensure that there is no foreign matter on the
switches, in the switch terminal groove, and
between copper bars above the switches.
4.
Ensure that there is no foreign matter on the
bottom plate of the cabinet.
5.
Ensure that there is no foreign matter on the
rear module subrack.