UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
5 Operations
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
164
Single/Parallel
and
Output frequency
must be correctly set. Otherwise, the UPS running
may be affected.
Output voltage level
refers to the line voltage level.
Figure 5-1
Settings Wizard
Set the time and date correctly. Incorrect time and date will cause false fault analysis during
maintenance or repair.
After you set network parameters, connect the UPS to the network over a network cable, which
enables you to remotely manage the UPS. If you do not need remote management, retain the default
network parameter settings.
Step 2
(Optional) On the MDU, choose
System Info
>
Settings
>
DST Settings
and set the DST
mode as required.
Step 3
After you set parameters on the
Settings Wizard
screen, the MDU displays the
Bypass mode
and
No battery
alarms, which do not need to be handled. If there is any other alarm, you need
to rectify the fault.
After you set parameters on the
Settings Wizard
screen, choose
System Info
>
Settings
>
System
Settings
. Check that
Requisite modules
and
Redundant modules
match the actual values.