UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
132
Perform operations as prompted.
Before starting the wizard, ensure that:
The system is a single UPS system.
No minor or critical alarm occurs.
The UPS works in normal mode with a load ratio fluctuation less than 10%.
The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
SOC > 30%
Figure 4-40
Wizard-based startup
On the
Settings
>
Dry Contact Set
screen, set
MUE05A connection
to
Enable
, and set
BCB
connection [OL]
to
Enable
. Wizard-based startup can be used to test the battery switch tripping
function.
4.1.2.6 About
On the
About
screen, you can view the model, manufacturer, monitoring version, and power
version. To view version details, tap
Version Info
.