UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
8 Technical Specifications
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
197
Item
Specifications
Output
voltage
unbalance
Voltage unbalance: ±3%; phase unbalance: ±2°
Overload
capability
Inverter overload capability:
105% < linear load ≤ 110%: transfer to bypass mode after 60 min
0°C ≤ ambient temperature ≤ 30°C, 110% < linear load ≤ 125%,
transfer to bypass mode after 10 minutes.
30°C < ambient temperature ≤ 40°C, 110% < linear load ≤ 125%,
transfer to bypass mode after 3 minutes.
125% < linear load ≤ 150%: transfer to bypass mode after 30 seconds.
Linear load > 150%, and short circuit: run for 200 ms.
Table 8-9
System Electrical Specifications
Item
Specifications
Redundancy
design
Control units and parallel signals use a redundancy design.
ECO
Supported