4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
144
Item
Description
Default Value Value Range
the rack.
Bat mode shut
In battery mode, the UPS can
automatically power off
according to the preset shutdown
delay time. If the parameter is
disabled, this function is not
available.
Disable
Disable, Enable
Backup time
warning
An alarm is generated if this
parameter is set to
Enable
and
the backup time is less than the
warning threshold.
Disable
Disable, Enable
Remain. cap.
warning
An alarm is generated if this
parameter is set to
Enable
and
the remaining capacity is less
than the warning threshold.
Disable
Disable, Enable
Intelligent
hibernation
If this parameter is set to
Enable
,
the intelligent battery hibernation
function is enabled.
Disable
Disable, Enable
Thres. of low
batt. SOC over
dry contact (%)
If an output dry contact is set to
Low battery SOC
, and the
battery SOC is lower than this
threshold, the output dry contact
will output signals.
75
5–80
Thres. of low
batt. volt. over
dry contact
(V/cell)
If an output dry contact is set to
Batt. Volt. Below Threshold
,
and the battery voltage is lower
than this threshold, the output dry
contact will output signals.
1.70
1.70–2.10
4.2.2.2 Communication Settings
Figure 4-48
Communication settings