Figure 2-17
600kVA bypass module
(1) Positioning
lock
(2) Ready switch
(3) Fault
indicator
(4) Alarm indicator
(5) Run indicator
(6) Cold start
button
(7) Crowbar
(8) Auxiliary power
supply
Table 2-3
Indicator description
Indicator
Color
Status
Description
Run indicator
Green
Steady on
The system is working in
bypass mode.
Blinking at long
intervals
The bypass has no output
(blinking at 0.2 Hz, on for
2.5s and off for 2.5s).
Blinking at short
intervals
The bypass is not configured
or the DSP software is being
upgraded (blinking at 4 Hz,
on for 0.125s and off for
0.125s).
Off
The bypass CPLD software is
being upgraded.
Alarm indicator
Yellow
Steady on
A minor alarm is generated
for the bypass.
Off
There is no minor alarm for
the bypass, or the CPLD
software is being upgraded.