UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
117
Item
Description
Default Value Value Range
power module
start delay (s)
UPS to control the interval that
each rack (or module) transfers
from battery mode to normal
mode, which reduces the impact
on the generator or power grid. In
the case of battery undervoltage,
the system automatically shortens
the delay for transferring to
normal mode to 1/8 of the normal
delay to accelerate the transfer
and prevent battery
overdischarge.
Intra-rack power
module start delay (s)
can be set
to a value ranging from 0.5 to
120.
Inter-rack power module
start delay (s)
can be set to a
value ranging from 2 to 120. The
preset value of
Inter-rack power
module start delay (s)
is 5.0.
The start delay of a module in a
rack varies depending on the rack
number and module number. #1
module in rack 1 does not have a
start delay.
value of this
parameter
depends on the
default number
of power
modules. The
default value is
2.0, 1.0, and 0.5
for 1–5, 6–10,
and 10–20
power modules
respectively.
Inter-rack
power module
start delay (s)
5
2–120
NTC
The short-distance battery
temperature sensor monitors the
ambient temperature near
batteries, and ensures that
batteries work reliably and
securely.
Disable
Disable, Enable
BCB trips if
UPS stops
power supply
N/A
Enable
Disable, Enable