Button
Exterior
SW button
When the smart cooling product is shut down and the
admin user has logged in, if you hold down the button for
more than 10s, a red frame is added to the button that
involves a risky operation on the display module within 5
minutes. You can press and hold down the button for 10s
to enter the risky operation screen. Exercise caution
because a risky operation may affect system data.
2.4 Monitoring System
The monitoring system provides logic control, data collection, control demand
delivering, alarm reporting, data storage, user right management, and teamwork
control. You can connect the smart cooling product monitoring system to your
monitoring system over a northbound communications port to perform remote
management. The smart cooling product supports remote management ports and
provides RS485 ports and FE ports to support Modbus-RTU, Modbus-TCP and
SNMP for real-time data collection and alarm reporting.
Smart cooling products can be networked over the CAN bus to realize teamwork
control, energy conservation, and service life extension.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
2 Product Description
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
29