Menu
Name
Parameter Description
Default Value
Heating mode
If Dehumidifying heating
is selected, the electric
heater determines whether
to start based on the
current temperature only
when the dehumidification
function is enabled. If Low-
temperature heating is
selected, the electric heater
is started only based on
temperature requirements,
regardless of whether the
dehumidification function
is enabled. If Dehumid &
low-temp heat is selected,
the electric heater
determines whether to
start based on the
temperature requirements
when the dehumidification
and heating conditions are
met.
Dehumid &
low-temp heat
Humidifying
function
If Enable is selected, the
device starts humidifying
when the ambient
humidity is lower than the
humidity setpoint by a
certain range. If Disable is
selected, the humidifying
function is disabled. If
Enabled when active
power is selected, the
device starts humidifying
when the ambient
humidity is lower than the
humidity setpoint by a
certain range and when the
active power supply is
used.
Enable
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual