Menu
Name
Parameter Description
Default Value
Settings >
Alarm
Settings >
Mainboard
Return air filter
blocked alarm
● Enable: Alarms are
reported to the NMS.
Active alarms are
displayed on the display
module and the system
performs related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
Enable
Primary power
failure alarm
● Enable: Alarms are
reported to the NMS.
Active alarms are
displayed on the display
module and the system
performs related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
Enable
Settings >
Alarm
Settings >
Chilled
water valve
Supply water
temperature
sensor alarm
● Enable: Alarms are
reported to the NMS.
Active alarms are
displayed on the display
module and the system
performs related
protection actions.
● Disable: Alarms are not
reported and no
protection actions are
implemented.
Enable
Supply water high
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
25.0°C
Supply water low
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
0.0°C
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
E Parameter Description
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
229