Parameter Description
Default Value
Supply air low
temperature
alarm
An alarm is generated
when the detected value is
less than the corresponding
threshold.
5.0°C
Return air high
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
45.0°C
Return air low
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
15.0°C
Cold aisle high
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
40.0°C
Cold aisle low
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
10.0°C
Hot aisle high
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
45.0°C
Hot aisle low
temperature
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
15.0°C
High humidity
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
85.0%RH
Low humidity
alarm
An alarm is generated
when the system detects
that the value exceeds the
corresponding threshold.
20.0%RH
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
E Parameter Description