Menu
Name
Parameter Description
Default Value
Humidifying
function
If Enable is selected, the
device starts humidifying
when the ambient
humidity is lower than the
humidity setpoint by a
certain range. If Disable is
selected, the humidifying
function is disabled. If
Enabled when active
power is selected, the
device starts humidifying
when the ambient
humidity is lower than the
humidity setpoint by a
certain range and when the
active power supply is
used.
Enable
Humidifying
Specifies the starting mode
of the humidifier.
Humidifying
only
Dehumidifying
function
If this parameter is set to
Enable, the device starts
dehumidification when the
ambient humidity is higher
than the preset humidity
threshold for a certain
range. If this parameter is
set to Disable, the device
does not start
dehumidification. If this
parameter is set to
Enabled when active
power, the device starts
dehumidification when the
ambient humidity is higher
than the preset humidity
threshold for a certain
range and when the
primary power is supplied.
Enable
Supply air temp
to forcibly start
cooling
Specifies the temperature
threshold for forcibly
starting the compressor
when the supply air
temperature is higher than
the threshold.
25.0°C
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
E Parameter Description
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
238