Figure 3-29 Connecting the drainpipe for a downflow unit
(1) Drainpipe
●
Port reserved in the equipment: G 3/4 inch port with internal threads
●
Onsite connection: G 3/4 inch port connected to a PPR rigid pipe through
external threads
3.5.5 (Optional) Installing the Water Inlet Pipe for the Wet
Film Humidifier
NO TICE
Install a water filtering device at the port of the water inlet pipe for the wet film
humidifier.
The following figure uses a rigid pipe as an example.
Figure 3-30 Water inlet pipe
●
Port reserved in the device: G 1/2 in. port with outer threads.
●
Onsite connection: Connect a pipe with a G 1/2 in. port and inner threads to
the port reserved in the device. A stop valve needs to be installed at the water
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
58