6.1.1 Monthly Maintenance
This section describes routine maintenance items for an indoor unit. Record
maintenance results in the table after a maintenance item is complete.
Table 6-1 Monthly Maintenance
Maintenan
ce Item
Operation
Troubleshooting
Air filter
Check that the air filter is
clean and not blocked.
Clean the air filter.
Check that the air filter is
not damaged or distorted.
Replace the air filter (It is
recommended that an air filter
should be replaced every 6
months).
Indoor fan
Check that the indoor fan
guard is not distorted.
Repair or replace the fan guard.
Check that the indoor fan
blades are intact.
Replace the fan.
Check that no foreign
matter exists in the fan.
Clear foreign matter.
Check that the indoor fan
generates no abnormal
sound during operation,
such as metal friction sound
and harsh noises.
Clear foreign matter and check
that screws securing the fan are
tightened.
Check that the screws on
the indoor fan are not loose
or distorted.
Tighten or replace the screws.
Water pan
Water pan is not blocked.
Clean the water pan.
Wet film
humidifier
Check that no operating
overtime alarm is generated
on the wet film humidifier.
Replace the wet film humidifier (It
is recommended that an air filter
should be replaced every 12
months).
Chilled
water valve
Check that the chilled water
valve is secure and that the
actuator cable is connected
securely.
Secure the chilled water valve and
the actuator cable.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
135