Table 3-8 Description about the cables of the NetCol8000-C130/NetCol8000-C190
Applica
tion
Scenari
o
Name
Technical Requirements
Remarks
Indoor
unit
Power cable
(without
heating and
humidification)
Electrical power cable, 600
V/1000 V, ZA-RVV, 5 x 4
mm
2
, black (five core wires:
red, yellow, green, blue,
black), 32 A, outdoor cable,
CE
The length is
determined based
on the pre-sales
engineering survey.
The neutral wire is
not required for the
power input to the
product. Cut the
blue neutral wire
onsite and wrap
the exposed part
using insulation
tape. You can also
purchase 4-core
power cables in
advance.
Power cable
(with heating
and
humidification)
Electrical power cable, 600
V/1000 V, ZA-RVV, 5 x 6
mm
2
, black (five core wires:
red, yellow, green, blue,
black), 32 A, outdoor cable,
CE
The length is
determined based
on the pre-sales
engineering survey.
The neutral wire is
not required for the
power input to the
product. Cut the
blue neutral wire
onsite and wrap
the exposed part
using insulation
tape. You can also
purchase 4-core
power cables in
advance.
Equipotential
ground cable
Greater than or equal to 6
mm
2
The length is
determined based
on engineering
survey.
Teamwo
rk and
monitor
ing
network
cables
Standard
network cable
Signal cable, shielded
straight-through cable, 10 m,
MP8-II, CC4P0.5GY(S), MP8-
II, FTP
The length is
determined based
on engineering
survey.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
3 Installation
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
42