Symptom
Possible Cause
Troubleshooting
The temperature and
humidity thresholds are
improper.
Adjust the temperature and
humidity thresholds.
Alarms, such as water
overflow and no
refrigerant output, are
generated.
Check the alarm causes and
clear the alarm manually.
The chilled water valve
is faulty or the cable
connection is incorrect.
Replace the actuator or
reconnect the cable.
The
FusionCol8000-C
leaks at the
bottom.
The thermal insulation
foam of the
NetCol8000-C is
damaged.
Check whether thermal
insulation foam of the
NetCol8000-C is securely
installed and repair the
damaged thermal insulation
tube.
The drainpipe is blocked. Ensure that the drainpipes are
not over-bent and the drainpipe
connectors are securely installed.
The pipes leak.
Check the pipes and weld the
pipe or fasten related bolts if the
pipes leak.
The water inlet solenoid
valve cannot be closed.
Replace the water inlet solenoid
valve.
Drainage capacity
of the
NetCol8000-C
decreases.
The drainpipe is bend or
trapped.
Check that drainpipes are free
from bends and traps. Ensure
that the height difference for
drainage is enough.
The heating
function fails.
The electric heater
temperature switch is
being protected.
Check whether the temperature
switch is faulty. Replace the
faulty switch.
An electric heater is
burnt out.
Disconnect the power supply
and check whether the electric
heater is damaged by checking
the electric heater resistance
properties with an ohmmeter.
No water is
supplied to the
water inlet
solenoid valve of
the humidifier.
The upstream water
supply is faulty or the
water pressure is below
the lower threshold.
Restore the water supply.
The water inlet solenoid
valve is blocked or
faulty.
Replace the water inlet solenoid
valve.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
161