6.4.9 Replacing an Inlet Solenoid Valve
Context
Recommended tools and materials: Phillips screwdriver and a new inlet solenoid
valve
Procedure
Step 1 Tap Shutdown on the home screen of the display module.
NO TICE
Exercise caution because the device is still energized after it is shut down on the
screen of the display module.
Step 2 Open the front door and turn off the general switch. For a device that has two
power inputs, turn off the active power switch QF1 and standby power switch
QF2.
Step 3 Turn off the water injection valve of the inlet solenoid valve.
Step 4 Unplug the cable terminals (YV4.1 and YV4.2).
Step 5 Use the Phillips screwdriver to remove the 2 fastening screws of the sheet metal.
Take out the inlet solenoid valve.
Figure 6-31 Removing the screws securing the sheet metal of the water inlet
solenoid valve
Step 6 Remove the intake tube of the inlet solenoid valve.
Step 7 Install a new inlet solenoid valve by performing
to
.
----End
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.