Alarm ID
Alarm Name
Alarm
Severity
Possible Cause
Solution
A27C-01
A27C-02
Return air 1 temp/
humid sensor fault
Return air 2 temp/
humid sensor fault
Return air 3 temp/
humid sensor fault
Return air 4 temp/
humid sensor fault
Return air damper 1
temp/humid sensor
fault
Cold aisle 1 temp/
humid sensor fault
Cold aisle 2 temp/
humid sensor fault
Cold aisle 3 temp/
humid sensor fault
Cold aisle 4 temp/
humid sensor fault
Cold aisle 5 temp/
humid sensor fault
Hot aisle 1 temp/
humid sensor fault
Hot aisle 2 temp/
humid sensor fault
Hot aisle 3 temp/
humid sensor fault
Hot aisle 4 temp/
humid sensor fault
Hot aisle 5 temp/
humid sensor fault
Fresh air 1 temp/
humid sensor fault
Major
● The cables to the
temperature and
humidity sensor are
loose or damaged.
● The temperature
and humidity
sensor is faulty.
1. Check the cables to
the temperature
and humidity
sensor.
2. Maintain or replace
the temperature
and humidity
sensor.
A27F-02
Water overflow alarm
Critical
The water overflow
sensor detects water
or the sensor is faulty.
If the water overflow
sensor is configured,
check and clear the
water source, and
maintain or replace
the sensor.
NetCol8000-C(070, 130, 190) In-room Chilled Water
Smart Cooling Product
User Manual
6 Maintenance
Issue 07 (2021-12-30)
Copyright © Huawei Technologies Co., Ltd.
157