IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
5 Parts Replacement
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
95
Figure 5-14
Removing a point-type water sensor
Step 3
Install a new water sensor and tighten the screws.
Step 4
Connect cables to the water sensor.
Step 5
Check that the new water sensor is working properly.
Drip a small amount of water onto the water sensor. If the monitoring software terminal generates an
alarm, the water sensor is working properly.
----End
Follow-up Procedure
Dispose of the removed water sensor that is confirmed faulty.
5.3.3 Replacing a Water Sensor (Rope Type)
Prerequisites
A water sensor needs to be replaced.
Spare water sensors of the same model are available and functional.
Impact on the System
None
Preparations
Tools: Phillips screwdriver, protective gloves
Material: spare water sensor
Document required: monitoring device layout diagram
Skill requirement: weak-current engineer