IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
6 Emergency Operations
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
162
If smoke or fire exists, go to
Step 3
Check whether fire extinguishing agent has been released.
If the system has started releasing fire extinguishing agent, wait until the fire is
extinguished and contact Huawei technical support.
If the fire extinguishing agent has not been released, check the situation onsite and
contact the local fire station.
Step 4
Take necessary tools and communications devices, arrive at the site as soon as possible, open
the external fire control box, and press the emergency start button.
Remove the yellow cover on the fire control panel, press the start switch, leave the site
immediately, and wait for the firefighters to handle the situation.
If a container is on fire, do not enter the container or stay around the container before the
fire is extinguished.
Step 5
Check whether there is an alarm on the fire control panel outside the container.
Step 6
If the fire control panel reports no composite fire alarm, check the cable connection from the
fire control panel to the management system.
If the cable connection is correct and the alarm disappears, the troubleshooting ends.
If the cable connection is correct but the alarm persists, go to
Step 7
Check the threshold settings for the fire control panel in the management system.
If the settings are correct and the alarm disappears, the troubleshooting ends.
If the settings are correct but the alarm persists, contact Huawei technical support.
----End
Follow-up Procedure
Analyze the cause of the fault, and work out and record the preventive measures.