4 Alarms and Faults
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
56
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
The onsite humidity
is too low.
The
humidification
function of air
conditioners is
abnormal.
Troubleshoot by
following instructions
in the air conditioner
user manual.
4.11 Door Status Alarm
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
Door open
alarm
Critical
No container door is
open.
The sensor is
incorrectly set.
Reset the door status
sensor.
The sensor is
faulty.
Replace by following
instructions in
Replacing a Door Status
Sensor
A container door is
open.
The container
door is open.
1.
Close the door and
check whether the
alarm is cleared.
2.
If the alarm persists,
troubleshoot by
following
instructions in
Emergency
Operations for
Container Door
Open
4.12 Door Status Alarms
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
Door
status
alarms
Critical
The door status
cannot be
controlled.
The access
controller is
faulty.
Verify the access
controller cable
connections, or replace
it by following
instructions in