Procedure
Step 1
Locate the water sensor to be replaced based on the alarm information on the monitoring
software terminal.
shows a rope-type water sensor.
Figure 5-15
Rope-type water sensor
Step 2
Remove the signal cable and extension cable, as shown in
Figure 5-16
Removing the signal cable
Step 3
Remove the screws tightening the faulty water sensor using a Phillips screwdriver, and
remove the water sensor.
Step 4
Install a new water sensor and tighten the screws.
Step 5
Connect the signal cable and extension cable for the water sensor in reverse order of
Step 6
Check that the new water sensor is working properly.
Dip the water detection cable into water. If the monitoring software terminal generates an alarm, the
water sensor is working properly.
----End