4 Alarms and Faults
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
67
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
Major
The heating
function does not
work.
The electric
heater
temperature
switch is
protected.
Check the temperature
switch and replace it if
it is faulty.
The electric heater
circuit breaker is
switched off.
The electric
heater circuit
breaker is
switched off.
Check the electric
heater circuit breaker.
The electric heater
burns out.
The electric
heater burns
out.
Disconnect the power
supply and check
whether the heater is
damaged by measuring
its resistance with a
multimeter.
Major
Water overflows.
The drainpipe
is not
connected to
the pump, or
the lift of the
condensate
pump does not
match the
height of the
pipes.
Ensure that the
drainpipe is correctly
connected to the pump,
and that the height of
the drainpipe is lower
than 3.5 meters.
The water
pump circuit
breaker or
cable
connection is
faulty.
Check the circuit
breaker status and cable
connections.
The water
pump is faulty.
1.
Check the alarms
displayed.
2.
Verify pump cable
connections.
3.
Rotate the pump
exhaust plug to
expel air, and close
the plug.
4.
Check whether the
water pump is
working properly.