IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
23
Item
Method
Expected Result
Troubleshooting
ATS
controller
Observe the LCD of
the ATS controller.
The ATS controller LCD
displays information
clearly.
If the LCD displays
no information or the
information
displayed is not clear,
check whether the
power cable to the
ATS controller is
properly connected.
If the problem
persists after the
power cable is
properly connected,
replace the ATS
controller. For details
about how to replace
the ATS controller,
contact Huawei
technical support.
3.3.2 Cooling System
Table 3-9
Quarterly maintenance checklist for the cooling system
Item
Method
Expected Result Troubleshooting
20 kW
air-cooled
precision
air
conditioner
Check the indoor
fans.
The fan cover is
not misshapen.
Replace the indoor fan by
following instructions in the air
conditioner user manual.
The fan blades are
intact.
Replace the indoor fan by
following instructions in the air
conditioner user manual.
Check the running
sound of the indoor
fan.
No abnormal
noise is generated.
Replace the indoor fan by
following instructions in the air
conditioner user manual.
Check screws
securing the indoor
fan.
The indoor fan is
securely installed.
Tighten screws securing the
indoor fan.
Check air filters.
The air filters are
blocked.
Clean dust from the air filters
using a brush or vacuum cleaner.
The air filters are
not damaged or
misshapen.
Replace by following
instructions in
Air Filters for a 20 kW
Air-cooled Precision Air
Conditioner