IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9
Catego
ry
Item
Method
Expected
Result
Troubleshooting
If the camera is normal
but no video image is
displayed:
1.
Connect the VCN500
cable again.
2.
If the cable is
correctly connected,
replace the camera by
following instructions
in
The coverage of
the camera is
optimal.
If the camera coverage
does not meet the
monitoring requirement,
adjust the camera
coverage.
Access
controller
communi
cation
status
Check the door
status list in the
management
system, and verify
whether the access
controller is
working properly.
After
configuring the
access controller
in the
management
system, you can
check the access
controller
working status
by viewing the
door status list
in the
management
system. If all
door status icons
under an access
controller blink,
the access
controller is
working
properly.
If a door status icon is
dimmed (unavailable),
check the access
controller and network
status.
Fire
extingui
shing
system
VESDA
and its
power
supply
Check the working
status of the
VESDA and its
power supply.
The VESDA
and its power
supply are
normal.
If the VESDA or its
power supply is
abnormal, troubleshoot
by following instructions
in documents delivered
with the VESDA.