IDS1000-A Air-Cooled Container Data Center
All-in-One Maintenance Guide
3 Maintenance
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
33
Item
Method
Expected
Result
Troubleshooting
Access
control
system
(Optional) Check
the magnetic lock
indicator.
The indicator
turns red
when the
container
door is
opened.
The indicator
turns green
when the
container
door is
closed.
If the indicator status is incorrect,
replace by following instructions
in
(Optional) Check
the electronic lock
indicator.
The indicator
turns red when
the container
door is opened.
The indicator
turns green when
the container
door is closed.
If the indicator status is incorrect,
replace by following instructions
in
Press down the
button after
removing the glass
cover of the
emergency door
release button.
The container
door can be
opened.
If the container door cannot be
opened, replace by following
instructions in
an Emergency Door Release
Button
Press the exit
button and open
the door.
The door can be
opened.
1.
Check whether the cable to the
exit button is properly
connected.
2.
If the fault persists, replace by
following instructions in
5.3.13.2 Replacing an Exit
Button
Swipe a card to
open the door.
When an access
card is swiped,
the card reader
indicator
becomes red for
3s (you will bear
a beep) and then
returns to steady
blue.
Swipe another access card and
observe the door status:
If the door can be opened by
another access card, the
original access card is
damaged. Prepare a new
access card and assign
permission to the card.
If the door cannot be opened,
replace by following
instructions in