4 Alarms and Faults
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
54
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
An air
conditioner
component is
faulty.
Replace the faulty
component by
following instructions
in the air conditioner
user manual.
The power load
exceeds the
designed
cooling
capacity.
For details, see
The onsite
temperature is
normal.
The T/H sensor
is faulty.
Replace by following
instructions in
Undertem
perature
Informati
on
The onsite
temperature is too
low.
The load ratio
is too low.
Shut down some air
conditioners.
The onsite ambient
temperature is too
low.
The air supply
temperature is
set too low.
Verify that the initial
configurations of the
air-cooled precision air
conditioner are
consistent with the
initial configuration
requirements initial
configuration guide.
The onsite
temperature is
normal.
The T/H sensor
is faulty.
Replace by following
instructions in