COMBI521
EN - 97
Test 3
Status check of the EVSE system
The purpose of this test (consisting in 6 steps) is checking all internal statuses of the
EVSE
system according to the prescriptions of the reference standards, carrying out
simulations with connected accessory
EV-TEST100
. The situations considered are the
following:
Status
Select.
CP
Select.
PP
Select.
FAULT
Ventilation
Parameters
checked
Result
OK
Result
NO OK
A
A
NC
OK
ON or OFF
VL1N
≤
10V >10V
VL1-PE
≤
10V >10V
VN-PE
≤
10V >10V
VCP (peak)
12V±0.6V
out of range
Frequency DC
(0Hz)
>0Hz
Charge current
≤
0A >0A
B B
Rated
current
OK
ON or OFF
Plug check
Plug blocked
Plug released
B B
Rated
current
OK
ON or OFF
VL1N
≤
10V >10V
VL1-PE
≤
10V >10V
VN-PE
≤
10V >10V
VCP (peak)
9V±0.6V
out of range
Frequency DC
(0Hz)
>0Hz
Charge current
≤
0A >0A
C C
Rated
current
OK OFF
VL1N Vnom±10%
out of range
VL1-PE Vnom±10%
VN-PE
≤
25V >25V
VCP (peak)
6V±0.53V
out of range
Frequency
1kHz±0.5%
out of range
Charge current Selected current
-
D D
Rated
current
OK ON
VL1N Vnom±10%
out of range
VL1-PE Vnom±10%
VN-PE
≤
25V >25V
VCP (peak)
3V±0.6V
out of range
Frequency
1kHz±0.5%
out of range
Charge current Selected current
-
FPE C
Rated
current
PE
ON or OFF
VL1N
≤
10V >10V
VL1-PE
≤
10V >10V
VN-PE
≤
10V >10V
VCP (peak)
≤
11V >11V
Frequency DC
(0Hz)
>0Hz
Charge current
≤
0A >0A
FE C
Rated
current
E
ON or OFF
VL1N
≤
10V >10V
VL1-PE
≤
10V >10V
VN-PE
≤
10V >10V
VCP (peak)
≤
11V >11V
Frequency DC
(0Hz)
>0Hz
Charge current
≤
0A >0A
Table 3: List of considered situations when checking statuses