COMBI521
EN - 103
48. Press the
GO/STOP
key. The result of measurements is
shown in the screen on the side. The instrument displays
the message "
OK
" in case of a positive result of the tests
(see Table 3)
STS
15/10 – 18:04
L1-N
= 230 V CP = 3.0 V
L1-PE
= 230 V F
= 1000 Hz
N-PE
= 0 V I
= 13.0 A
OK
D
STATUS
49.
Press the
SAVE
key to partially save the test, and to carry on with the subsequent test
for the
simulation of a fault on PE
(no. 52).
50. The instrument displays the message "
FAIL
" in case of a
negative result of at least one test (see Table 3)
STS
15/10 – 18:04
L 1 -
N
=
2 3 0
V
C P =
3 . 0
V
L 1 -
P E
=
1 9 1
V
F =
1 0 0 0
H z
N -
P E
=
0
V
I =
1 3 . 0
A
FAIL
D
STATUS
51. Press the
SAVE
key to partially save the test and to
end
the sequence of tests
. The instrument shows the
message contained in the following screen for a few
seconds.
Repeat the sequence again, if necessary.
STS
15/10 – 18:04
Sequence completed
D
STATUS
52. Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
to input
N
, input
B3
to
input
E
and input
B1
to input
L1
).
Use the three
selectors of the adapter and set the following
positions:
PP State
13A,20A,32A
or
63A
CP State
C
Fault
PE
STS
15/10 – 18:04
3/6 – Checking FAULT PE