7. At the end of the test, if the detected phase sequence is
incorrect, the instrument displays a screen like the one
shown to the side (result "
213
") and the “
NOT
OK
”
message.
1 2 3
15/10 – 18:04
TN
2 1 3
NOT OK
1T
MODE
8. At the end of the test, if the two detected voltages are in
phase (
phase concordance between two distinct
three-phase systems
), the instrument displays a screen
like the one to the side (result "
11-
") and the “
OK
”
message.
1 2 3
15/10 – 18:04
TN
1 1 -
OK
1T
MODE
9. Press the
SAVE
key to store the test result in the instrument’s memory (see § 7.1) or
the
ESC/MENU
key to exit the screen without saving and go back to the main
measuring screen.