MEASUREMENT OF NETWORK PARAMETERS AND HARMONICS
DC Voltage
Range [V]
Resolution [V]
Accuracy
15.0
265.0
0.1V
(1.0
rdg + 1dgt)
Values lower 15V are zeroed
AC TRMS Voltage
Range [V]
Frequency [Hz]
Resolution [V]
Accuracy
15.0
459.9
50/60Hz ±5%
0.1V
(1.0
rdg + 1dgt)
Values lower 15V are zeroed; Max crest factor: 1.5
Frequency
Range [Hz]
Resolution [Hz]
Accuracy
47.5
63.0
0.01
(2.0
rdg + 2dgt)
Allowed voltage range: 5.0
459.9V ; Allowed current range:
≥
5mVAC
DC Current with transducer clamp (In1 input – STD clamp)
Range [mV]
Resolution
[mV] Accuracy
-1999.9
-1.0
0.1
(5.0%rdg + 2dgt)
1.0
1999.9
Values lower to ±1mVDC are zeroed
AC TRMS Current with transducer clamp (In1 input – STD clamp)
Range [mV]
Frequency [Hz]
Resolution
[mV] Accuracy
1.0
2999.9
50/60Hz ±5%
0.1
(5.0%rdg + 2dgt)
Values lower to 1mVAC are zeroed ; Max crest factor: 3
DC/AC TRMS current with transducer clamp (In1 input – STD clamp)
FS clamp / Output ratio
Measurement range
Resolution
1A/1V AC
0.1mA ÷ 999.9mA AC
0.1mA AC
5A/1V AC
0.001A ÷ 4.999A AC
0.001A AC
10A/1V AC/DC
0.001A ÷ 9.999A AC/DC
0.001A AC/DC
30A/3V AC
0.01A ÷ 29.99A AC
0.01A AC
40A/400mV AC/DC
0.01A ÷ 39.99A AC/DC
0.01A AC/DC
100A/1V AC/DC
0.01A ÷ 99.99A AC/DC
0.01A AC/DC
200A/1V AC
0.01A ÷ 199.99A AC
0.01A AC
300A/3V AC
0.01A ÷ 299.99A AC
0.01A AC
400A/400mV AC/DC
0.1A ÷ 399.9A AC/DC
0.1A AC/DC
1000A/1V AC/DC
0.1A ÷ 999.9A AC/DC
0.1A AC/DC
2000A/1V AC
0.1A ÷ 1999.9A AC
0.1A AC
3000A/3V AC
0.1A ÷ 2999.9A AC
0.1A AC
DC Power
FS clamp
Range [W]
Resolution [kW]
Accuracy
10A
0.015
2.650k
0.001
(2.0
rdg + 5 dgt)
10A
FS
40
0.15
10.60k
0.01
40A
FS
100
0.15
26.50k
0.1
100A
FS
1000
1.5
265.0k
1
Active clamp (@ 230V single phase systems 1Ph, cos
=1, f=50/60Hz)
FS clamp
Range [kW]
Resolution [kW]
Accuracy
10A
0.000
9.999
0.001
(2.0
rdg + 5 dgt)
10A
FS
200
0.00
999.99
0.01
200A
FS
1000
0.0
999.9
0.1
1000A
FS
3000
0
9999
1