34. Connect the instrument to the adapter as shown in the
diagram on the display (input
B4
to input
N
, input
B3
to
input
E
and input
B1
to input
L1
).
Use the three
selectors of the adapter and set the following
positions:
PP State
13A,20A,32A
or
63A
CP State
B
Fault
OK
STS
15/10 – 18:04
3/6 – Checking status B
35. Press the
GO/STOP
key. The following screen appears
on the display. Notice the presence of the status “
B
”
corresponding to the position “STATUS”
STS
15/10 – 18:04
L1-N
= - - - V CP = - - - V
L1-PE
= - - - V F
= - - - Hz
N-PE
= - - - V I
= - - - A
B
STATUS
36. Press the
GO/STOP
key. The result of measurements is
shown in the screen on the side. The instrument displays
the message "
OK
" in case of a positive result of the tests
(see Table 3).
STS
15/10 – 18:04
L1-N
= 0 V CP = 9.1 V
L1-PE
= 3 V F
= 0 Hz
N-PE
= 3 V I
= 0.0 A
OK
B
STATUS
37.
Press the
SAVE
key to partially save the test, and to carry on with the subsequent test
(
no. 40 to check status C (non-ventilated EVSE system) or no. 46 to check status
D (ventilated EVSE system
).
38. The instrument displays the message "
FAIL
" in case of a
negative result of at least one test (see
Errore. L'origine
riferimento non è stata trovata.
).
STS
15/10 – 18:04
L1-N
= 0 V CP = 9.1 V
L1-PE = 15.6 V F
= 0 Hz
N-PE = 3 V I
= 0.0 A
FAIL
B
STATUS