53. Press the
GO/STOP
key to start the test
on PE status
.
The following screen appears on the display. Notice the
presence of the status “
FAULT PE
” corresponding to the
position “STATUS”
STS
15/10 – 18:04
L1-N
= - - - V CP = - - - V
L1-PE
= - - - V F
= - - - Hz
N-PE
= - - - V I
= - - - A
FAULT PE
STATUS
54. Press the
GO/STOP
key. The result of measurements is
shown in the screen on the side. The instrument
displays the message "
OK
" in case of a positive result of
the tests (see Table 3)
STS
15/10 – 18:04
L1-N
= 0 V CP = 11 V
L1-PE
= 0 V F
= 0 Hz
N-PE
= 0 V I
= 0.0 A
OK
FAULT PE
STATUS
55.
Press the
SAVE
key to partially save the test, and to carry on with the subsequent test
for the
simulation of a fault on E
(no. 58).
56. The instrument displays the message "
FAIL
" in case of
a negative result of at least one test (see Table 3)
STS
15/10 – 18:04
L1-N
= 0 V
CP = 11 V
L1-PE
= 0 V
F
= 0 Hz
N-PE
= 0 V
I
= 0.0 A
FAIL
FAULT PE
STATUS
57. Press the
SAVE
key to partially save the test and to
end
the sequence of tests
. The instrument shows the
message contained in the following screen for a few
seconds.
Repeat the sequence again, if necessary.
STS
15/10 – 18:04
Sequence completed
FAULT PE
STATUS