7. In case of
positive
result (contact voltage at the point
<50V or <25V), the “
OK
” message and the screen to the
side are displayed by the instrument. The screen contains
the value of the first fault current measured, expressed in
mA
(see § 12.9).
L O O P
15/10 – 18:04
IT
Ipfc
Ut
=
=
83
1
mA
V
FREQ. = 50.00Hz
VL-PE=232V
VL-N=234V
OK
L-PE Ut
FUNC
MODE
8. In case of
negative
result (contact voltage at the point
>50V or >25V), the “
NOT OK
” message and the screen
to the side are displayed by the instrument.
L O O P
15/10 – 18:04
IT
Ipfc
Ut
=
=
>999
>50
mA
V
FREQ. = 50.00Hz
VL-PE=232V
VL-N=234V
NOT OK
L-PE Ut
FUNC
MODE
9. Press the
SAVE
key to store the test result in the instrument’s memory (see § 7.1) or
the
ESC/MENU
key to exit the screen without saving and go back to the main
measuring screen.