COMBI521
EN - 70
6.7.10. Verification of protection against indirect contacts (TN systems)
9. Press the
MENU
key, move the cursor to
LOOP
in the
main menu by means of the arrow keys (
,
) and
confirm with
ENTER
. Subsequently, the instrument
displays a screen similar to the one reported here to the
side.Select “Europe” as a country (see § 5.1.2), the
options “TN”, “25 or 50V”, “50Hz or 60Hz” and the
reference voltage in the general settings of the instrument
(see § 5.1.3).
NOTE: for countries different from “Europe”, the
MCB and Fuse reference type can be changed.
L O O P
15/10 – 18:04
TN
min
pfc
I
ZL-PE
=
=
- - -
- - -
A
FREQ. = 0.00Hz
VL-PE=0V
VL-N=0V
L-PE Ut 16A 0.2s
FUNC
MODE MCB-C Time
10. Use the
,
keys to select the parameter to be modified, and the
,
keys to modify the
parameter value
FUNC
the virtual key allows setting the measuring mode of the instrument, which
may be
L-PE
MODE
the virtual key allows setting the instrument’s operating mode. Select the
Ut
option
Type of protection
the virtual key allows setting the type of protection (
Fuse
of
type
gG
,
aM
or magnetothermal
MCB
in curve
B, C, D, K
) and the relevant nominal
currents considering the below available values:
MCB curve B
3A, 6A, 10A, 13A, 15A, 16A, 20A, 25A, 32A, 40A, 45A, 50A, 63A,
80A, 100A, 125A, 160A, 200A
MCB curve C
0.5A, 1A, 1.6A, 2A, 3A, 4A, 6A, 10A, 13A, 15A, 16A, 20A, 25A,
32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A
MCB curve D, K
0.5A, 1A, 1.6A, 2A, 3A, 4A, 6A, 10A, 13A, 15A, 16A, 20A, 25A,
32A, 40A, 45A, 50A, 63A, 80A, 100A, 125A, 160A, 200A
Fuse gG
2A, 4A, 6A, 8A, 10A, 12A, 13A, 16A, 20A, 25A, 32A, 35A, 40A, 50A,
63A, 80A, 100A, 125A,160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A,
1250A
Fuse aM
2A, 4A, 6A, 10A, 12A, 16A, 20A, 25A, 32A, 35A, 40A, 50A, 63A, 80A,
100A, 125A, 160A, 200A, 250A, 315A, 400A, 500A, 630A
Time
the virtual key allows setting the protection’s tripping time among the
options:
0.1s
,
0.2s
,
0.4s
,
1s
,
5s
.
Press the
SAVE
key to save the selected parameter and go back to the
measurement screen
11. If possible, disconnect all loads connected downstream of the point to be measured, as
the impedance of these users could distort the test results. Perform the preliminary
calibration of the test leads as described in § 6.7.2.
12. Insert the green, blue and black connectors of the three-pin plug cable into the
corresponding inputs B3, B4 and B1 of the instrument. As an alternative, use the single
cables and apply the relevant alligator clips to the free ends of the cables. It is also
possible to use the remote switch probe by inserting its multipolar connector into the
input B1. Connect the Mains Plug, the alligator clips or the remote switch probe to the
electrical mains according to Fig. 22, Fig. 23, Fig. 24, Fig. 25 or Fig. 26
Содержание COMBI521
Страница 1: ... Copyright HT ITALIA 2021 Release EN 1 01 27 09 2021 COMBI521 User manual ...
Страница 143: ......