Chapter 7 Elevator Application Guidance
HD5L Series Controller User Manual V1.4
―
83
―
Asyn. motor parameter auto-tuning
1. Set F00.05 as 0 (keypad control).
2. Set F07.06 as 1 (stationary auto-tuning) or 2 (rotary auto-tuning), then press
key to start
parameter auto-tuning. The motor will rotate at rotary auto-tuning, while it will not rotate at stationary
auto-tuning.
Note:
When auto-tuning, it needs open the run contactor; if at rotary auto-tuning, it needs open the brake
contactor manually too.
7.1.4
Inspection Running
Before inspection running
Make sure the follow steps:
1. After motor parameter auto-tuning, motor output U/V/W connections and encoder connection are
not changed.
2. Set F03.06 (inspection Acc speed) and F03.07 (inspection Dec speed).
Inspection running
1. If the actual running direction of motor is not the command direction, set F00.08 (run direction) = 1.
2. Make sure that the motor can run normally.
3. Make sure the motor can run normally and the signals of the brake and power circuit etc. can act
normally, then it will do high speed running.
7.1.5
High Speed Running
1. Give the floor normal run command so that to the elevator can run normally. Then set Group F02 of
start & stop parameters, start stopping parameters, adjust starting & stopping brake and motor
running time sequence to make sure that the elevator does not shake at start & stop.
•
For asyn. motor, adjust Group F02 to avoid obviously shaking at start &stop.
•
For syn. motor, set Group F06 additionally to avoid elevator brake at start.
•
If syn. motor has SINCOS encoder, it can achieve elevator smooth start using weigh less method
(Group F06). And F02.02 (retention time of start zero-speed) is set at least as 0.5s.
2. If the elevator has slight shake at running, properly adjust Group F08.
3. To adjust leveling precision, Acc / Dec curve (Group F03) can adjust terminal MS control (F00.05 = 2)
to unify level and adjust F03.13 (stop Dec jerk) to make leveling precision.
7