Shenzhen Hpmont Technology Co., Ltd.
Chapter 6 Function Introduction
HD5L Series Controller User Manual V1.4
―
53
―
6.2.2
F01: Protection of Parameters
Ref. Code
Function Description
Setting Range [Default]
F01.00
User’s password
00000 - 65535 [00000]
XXXXX: To enable the password protection function, set any non-zero number as the password.
•
Once the password is set, and detect that there is no press on the keypad within 5 minutes, the user’s
password will be valid.
•
To change the parameters, input correct password. Otherwise can not change any parameter via
keypad, but only check.
00000: The factory setting and no user’s password.
•
If user unlocks the password, it means clearing the user’s password.
•
To unlock, change and clear the user’s password, refer to section 5.2.3.
F01.01 Menu
mode
0,1 [0]
0: Full menu mode. All parameters can be displayed.
1: Checking menu mode. Only parameters different from factory setting can be displayed.
F01.02
Function code parameter initialization
0 - 3 [0]
0: No operation. HD5L is in regular parameter read/write status.
•
Whether can change the parameter depends on the user’s password status and the actual operating
conditions of HD5L.
1: Restore to factory settings.
•
Except Group F01, F07.00 - F07.14, Group F10, Group F11, F15.00, F17.11 - F17.27, Group F18 and
Group Y.
•
Steps: If set F01.02 = 1, press
to ensure and the parameters are restored to factory settings. The
keypad dispalys “loading defualt para.”. Then the keypad will display parameters in stop status after
finish restoring to factory setting.
2: Parameter download.
•
Except Group F01, F17.11 - F17.27, Group F18 and Group Y.
•
Motor parameters, encoder parameters and magnetic pole angle etc. will be downloaded.
Record the original parameters such as motor parameters, encoder parameters and magnetic pole
angle etc. Or restart parameter auto-tuning.
3: Clear fault information. The fault history of F17.11 - F17.27 will be cleared.
F01.03
Keypad EEPROM parameter initialization
0,1 [0]
0: No operation. HD5L is in regular parameter read/write status.
1: Parameter upload. Upload the current function code settings to the keypad EEPROM parameter.
Note: Group F01, F17.11 - F17.27, Group F18 and Group Y do not upload.