Verifying the replacement procedure
Procedure
1.
Check the overall library status from the RMI
Status > Library Status
screen.
2.
Using the OCP or RMI, check for events. Verify that the event that indicated that the robotic assembly
or spooling mechanism was faulty has been cleared.
3.
If replacing the robotic assembly, upgrade the firmware if necessary.
The firmware for the robotic assembly is delivered with the library firmware. The replacement robotic
assembly might require a newer firmware version than currently installed on the library.
To find the version of firmware installed on the library, check the upper left corner of the RMI or the
About
screen on the OCP. Update the firmware from the RMI
Maintenance > Firmware Upgrades >
System Firmware
screen.
4.
Verify that the library detects all of the library components from the RMI
Status > Partition Map >
Configuration Status
screen.
If any expansion modules, power supplies, or tape drives are not detected, verify that all cords and
cables have been properly installed.
If using the MSL Encryption Kit, you might need to enter the token password.
5.
Run the robotic test from the RMI
Maintenance > Library Tests > Robotic Test
screen.
The robotic test performs a full inventory and exercises all robotic assembly movements and sensors.
6.
Resume host applications.
Replacing the rack shelves
Prerequisites
Tools required
• Small flat head or Torx screwdriver
• #2 Phillips screwdriver
• #3 Phillips screwdriver
Procedure
1.
2.
to lighten the module
3.
4.
Remove the module from the rack
5.
Remove the rack shelves from the rack
6.
Install the rack shelves in the rack
7.
Install the module in the rack
8.
Align and connect the library modules
Verifying the replacement procedure
159