Installation
2.1
Set-up
Space requirement of UltraGas
®
(125-1150)
(All dimensions in mm)
Fig. 01
UltraGas
®
Type
A
A minimum
B
C
D
H
H minimum
(125, 150)
180
1
80
2
820
1237
200
1823
1711
3
(200 - 300)
360
1
160
2
930
1584
200
1923
1811
3
(350 - 500)
200
1
100
2
1110
1679
200
2070
1958
3
(575 - 720) / H (720)
200
1
100
2
1290
1843
0
2086
1984
3
(850 - 1150) / H (1000)
420
1
230
2
1550
2154
0
2139
2037
3
1
If the room height is too low: the dimension can be reduced. See A
minimum.
2
Caution! At A minimum, the burner can no longer be swivelled out
completely! Cleaning is made difficult!
3
Feet can be shortened, no pedestal casing possible! For details see
next page.
For swinging out the burner
this area must remain free
(see dimension table)
If the gas line is routed horizon-
tally to the left, the minimum dis-
tance D must be observed.
The boiler can be placed with one side directly
the wall. For the casing to be installed, how-
ever, there must be a distance of at least 100
mm from the wall.
7
4 217 215 / 00
INSTALLATION