Guidance values for the flue gas pipe dimensions
Boiler
Flue gas line
(smooth walled)
Number of bow 90° (flue gas + air supply)
type
Flue gas dim. mm
Dimension
Total pipe length in m (flue gas + air supply)
UltraGas
®
internal
DN
1
2
3
4
5 *
(125)
155
130
24
23
22
21
(150)
155
15
14
13
12
(125)
155
150
44
44
44
44
(150)
155
44
44
44
44
(200)
252
24
24
23
22
(250)
252
12
12
11
11
(125)
155
175
50
50
50
50
(150)
155
50
50
50
50
(200)
252
50
50
50
50
(250)
252
46
45
45
44
(200)
252
200
50
50
50
50
(250)
252
50
50
50
50
(300)
252
50
50
50
50
(350)
302
42
41
40
39
(250)
252
250
50
50
50
50
(300)
252
50
50
50
50
(350)
302
50
50
50
50
(400)
302
50
50
50
50
(450)
302
50
50
50
50
(500)
302
50
50
50
50
(350)
302
300
50
50
50
50
(400)
302
50
50
50
50
(450)
302
50
50
50
50
(500)
302
50
50
50
50
(575)
302
50
50
50
50
(650)
302
50
50
50
50
(720)
302
50
50
50
50
(850)
402
350
50
50
50
50
(850)
402
400
50
50
50
50
(1000)
402
400
50
50
50
50
(1150)
402
400
50
50
50
50
Notice: The data contained in the table “Dimensions flue gas systems” represent guide values.
An exact calculation for the flue gas duct must be made on-site.
* With 5 bends or more the feed pressure total at the combustion air/flue gas line is to be reduced by 30% for the
calculation.
With total pipe lengths exceeding 50 m, a separate calculation is necessary.
26
4 217 215 / 00