Open the combustion chamber as described in
point 6.6.2 (cleaning the combustion chamber
and burner cylinder on the outside).
Cleaning:
Sand the ignition and ionisation devices with
fine sandpaper.
Clean away the sanding dust.
Check all electrode gaps and readjust if necessary
Readjusting procedure:
Heat the electrodes at the kink with the solder-
ing lamp until they glow red.
Use long-nose pliers to bend the ignition elec-
trodes until the required gap is set.
Ignition electrode
Ignition/ionisation electrode
4 mm
Fig. 38
10
±2 mm
4 mm
Fig. 39
Assembly:
Renew seal on gas connection.
Assemble burner in the reverse order.
Check for gas leaks.
6.6.4 Cleaning the gas filter HFVR050 (only applica-
ble for UltraGas
®
(450-720)) (if fitted)
[K]
[H]
Die Dichtheit der Verschraubungen
ist mittels Leckspray zu prüfen
Beim Eindichten aller Gasamaturen darf mit dem
Auftragen des Dichtungsmaterials frühstens beim
zweiten Gewindegang begonnen werden
UltraGas (575-720)
Aktiengesellschaft
Aenderungen
Gezeich.
Geprueft
Massstab
Ersetzt durch:
Ersatz fuer:
Werkst.-code
Werkstoffnr.
Gegenstand
Werkstoff
Bemerkung
3
6 034 324K-3
Umbauset Gasventil V434
26.09.13
26.09.13
GASI
GASI
Art.Nr.
00
%
Umbauset Gasventil V434
Verwendet
in :
31-UltraGas (575-720)
Masse ohne Toleranzangabe
siehe Hovalnorm HN 020400
Pos.10 Faltkarton 655x305x266
Pos.11 Anl. Umbauset Gasventil VR434
Pos.12 Rücksendeformular - Gasventil
2
1
4
,5
(
)
5 3 5 , 8
1
1
6
(
)
Gas filter
Gas valve
Fig. 40
The gas filter must be cleaned immediately after the in
-
itial commissioning and in occasion of the annual main-
tenance.
Clean the removed gas filter with clean running water and
reinstall it dry.
Replace the gas filter if it is not possible to clean it per
-
fectly.
After assembly, check the gas tightness (e.g. using a leak
detection spray).
50
4 217 215 / 00
MAINTENANCE