5.10 Type (850-1150) setting the stabilisation
damper (if required)
The stabilisation damper reduces the outlet cross section
of the blower during the starting phase. This optimises
the starting behaviour of the boiler! Factory setting of the
stroke: 20 mm.
This is the optimum setting with normal chimney condi-
tions.
If even stronger compression is required, the stroke can
be set to maximum 22.5 mm using the setscrew.
If lower compression is required, the stroke can be re-
duced using the setscrew. For example, 18 mm.
Stroke 20 mm
Setscrew
Fig. 28
5.11 Handover to the operator
The manufacturer of the unit is responsible
for providing operating instructions for the
complete system.
The following points must be carried out on the handover
to the owner:
• Instructions for operation, maintenance and safety
equipment of the machine.
• Handover all instructions and documents.
• Inform the owner that these instructions must always be
kept with the plant.
•
Written confirmation of the instruction.
• The handover report is on the last page of the docu-
ment.
42
4 217 215 / 00
COMMISSIONING