Parameter
Description
Unit
Level
System set
values
45-UG (500)
45-UG (575)
45-UG (650)
45-
UG (720)
45-
UG (850)
45-
UG (1000)
45-
UG (1
150)
34 2FM 32802 Downward ramp of the fan during operation
min
–1
/s OEM
100
100
100
100
100
100
100
35 2FN 32803 Post-venting of the fan after lock-out
sek OEM
180
180
180
180
180
180
180
36 2FO 32804 Fan speed after a normal switch-off
or after lock-out/blocking
min
–1
OEM
900 1000 1000 1000 900 1200 1600
37 2FR 32805 Fan afterrun time after operation or blocking
min OEM
3
3
3
3
3
3
3
38 2FU 32806 Fan speed at boiler freeze protection
min
–1
OEM
1500 1500 1500 1500 1500 1500 1600
39 2GA 32807 Waiting time after opening main gas valve
or activation of heating room fan
min OEM
0
0
0
0
0
0
0
40 2GB 32808 External main gas valve/
heating room fan available
OEM
1
1
1
1
1
1
1
41 2HA 32809 Afterrun heating pump or shut-off valve
min
HF
5
5
5
5
5
5
5
42 2HD 32810 Summer operation (“summer kick”)
sek OEM
10
10
10
10
10
10
10
43 2IA 32811 Ignition (0-> Internal, 1-> In External,
2-> External)
OEM
2
2
2
2
2
2
2
44 2KM 32812 Step modulation (0-> off, 1->increasing,
2-> increasing and decreasing)
HF
1
1
1
1
1
1
1
45 2LA 32813 Effect of the fault relay
HF
2
2
2
2
2
2
2
46 2NA 32814 ADC/4 value at 0 bar
OEM
25
25
25
25
25
25
25
47 2NB 32815
ADC/4 value at 6 bar and BIC 960 V.2
OEM
145
145
145
145
145
145
145
ADC/4 value at 10 bar and BIC 960 V.3
OEM
225
225
225
225
225
225
225
48 2IB 32816 Extended external ignition time
sek OEM
8
8
8
8
8
8
8
49 2CB 32817 Activate/deactivate vacuum and overpressure
switch (fan) (0 -> deactivated, 1 -> activated)
OEM
1
1
1
1
1
1
1
50 2CC 32818 Reserve
OEM
0
0
0
0
0
0
0
Adaptations for liquid gas
27 2FF 32795
Fan speed during the first period of pre-venting
min
–1
OEM
4100 3900 4400 4200 4200 5200
-
28 2FG 32796 Fan speed at start
min
–1
OEM
1800 1800 1800 2000 1700 1700
-
29 2FH 32797 Maximum fan speed
min
–1
OEM
4100 3900 4400 4200 4200 5200
-
30 2FI 32798 Minimum fan speed
min
–1
OEM
1300 1400 1400 1500 1300 1500
-
36 2FO 32804 Fan speed after a normal switch-off
or after lock-out/blocking
min
–1
OEM
1300 1400 1400 1500 1300 1500
-
56
4 217 215 / 00
PARAMETER LIST - AUTOMATIC FIRING DEVICE BIC 960
Содержание UltraGas 1000
Страница 57: ...57 4 217 215 00...