Type
(350)
(400)
(450)
(500)
(575)
(650)
• Nominal heat output at 80/60 °C, natural gas
kW
51-324
87-371
87-417
87-463
122-533
122-603
• Nominal heat output at 40/30 °C, natural gas
kW
58-350
97-400
97-450
97-500
136-575
136-650
• Nominal heat output at 80/60 °C, propane
2
kW
95-320
139-370
139-410
139-455
169-524
169-592
• Nominal heat output at 40/30 °C, propane
2
kW
109-350
154-400
154-450
154-500
185-575
185-650
• Nominal load with natural gas
1
kW
53-330
89-377
89-424
89-471
125-542
125-613
• Nominal load with propane
2
kW
100-330
144-377
144-424
144-471
175-542
175-613
• Working pressure heating maximum/minimum
bar
6.0/1.0
6.0/1.0
6.0/1.0
6.0/1.0
6.0/1.0
6.0/1.0
• Test pressure
bar
9.0
9.0
9.0
9.0
9.0
9.0
• Working temperature maximum
°C
90
90
90
90
90
90
• Boiler water content
l
428
411
387
375
549
529
•
Minimum water flow
l/h
0
0
0
0
0
0
• Boiler weight (without water content, incl. casing)
kg
881
922
972
991
1277
1303
•
Boiler efficiency at 80/60 °C in full-load operation (related to net
calorific value NCV/gross calorific value GCV)
%
98.2/88.5 98.3/88.6 98.3/88.6 98.3/88.6 98.3/88.6 98.3/88.6
•
Boiler efficiency at 30 % partial load (EN 15502) (related to net
calorific value NCV/gross calorific value GCV)
%
108.0/97.3 108.1/97.4 108.0/97.3 108.0/97.3 108.1/97.4 108.0/97.3
•
Standard efficiency
(DIN 4702-8)
40/30 °C
%
109.8/98.9 109.8/98.9 109.8/98.9 109.8/98.9 109.9/99.0 109.9/99.0
(related to net cal. value NCV/gross cal. value GCV)
75/60 °C
%
107.3/96.7 107.3/96.7 107.3/96.7 107.3/96.7 107.4/96.8 107.4/96.8
• Heat loss rate at 70 °C
Watt
750
750
750
750
1000
1000
• NOx class (EN 15502)
6
6
6
6
6
6
• Standard emission rate
Nitrogen oxides
mg/kWh
41
43
42
41
48
48
• Content of CO
2
in the flue gas maximum/minimum output
%
9.0/8.8
9.0/8.8
9,0/8.8
9.0/8.8
9.0/8.8
9.0/8.8
• Dimensions
see table of dimensions
• Connections
Flow/return
DN
DN
100/PN
6 DN
100/PN
6 DN
100/PN
6 DN
100/PN
6DN
125/PN
6DN
125/PN
6
Gas
inches
Rp 1½″
Rp 2″
Rp 2″
Rp 2″
Rp 2″
Rp 2″
Flue gas Ø inside
mm
302
302
302
302
302
302
•
Gas flow pressure
minimum/maximum
Natural gas E/LL
mbar
17.4-80
17.4-80
17.4-80
17.4-80
17.4-80
17.4-80
Propane
mbar
37-57
37-57
37-57
37-57
37-57
37-57
• Gas connection value at 15 °C/1013 mbar:
Natural gas E (Wo = 15.0 kWh/m
3
) NCV = 9.97 h/m
3
m
3
/h
32.6
37.7
42.4
47.1
54.2
61.3
Natural gas LL (Wo = 12.4 kWh/m
3
) NCV = 8.57 h/m
3
m
3
/h
38.0
44
49.5
55.0
63.2
71.5
Propane
3
(NCV = 25.9 kWh/m
3
)
m
3
/h
12.6
14.6
16.4
18.2
20.9
23.7
• Operation voltage
V/Hz
230/50
230/50
230/50
230/50
230/50
230/50
• Control voltage
V/Hz
24/50
24/50
24/50
24/50
24/50
24/50
• Electrical power consumption min./max.
Watt
46/328
58/442
58/580
68/790
59/720
59/1030
• Stand-by
Watt
12
12
12
12
12
12
• IP rating (integral protection)
IP
20
20
20
20
20
20
• Lowest ambient temperature during operation
°C
5
5
5
5
5
5
• Highest ambient temperature during operation
°C
40
40
40
40
40
40
• Sound power level
- Heating noise (EN 15036 part 1) (room air dependent)
dB(A)
74
71
73
75
72
75
- Exhaust noise is radiated from the mouth (DIN 45635 part 47) dB(A)
71
72
73
74
69
72
• Sound pressure level heating noise (depending on installation con-
ditions)
3
dB(A)
64
61
63
65
62
65
• Condensate quantity (natural gas) at 40/30 °C
l/h
30.6
35.4
39.9
44.3
50.9
57.6
• pH value of the condensate
approx.
4.2 approx.
4.2 approx.
4.2 approx.
4.2 approx.
4.2 approx.
4.2
• Flue gas system: requirements, values
Temperature class
T120
T120
T120
T120
T120
T120
Type of connection
B23P, C53
Flue gas mass flow at nominal heat load
kg/h
541
626
704
782
900
1018
Flue gas mass flow at lowest nominal heat load
kg/h
79.7
134
134
134
189
189
Flue gas temperat. at nominal output and operation 80/60 °C
°C
69
71
71
72
71
72
Flue gas temperat. at nominal output and operation 40/30 °C
°C
46
48
47
49
47
49
Flue gas temperat. at lowest nominal heat load and operation 40/30 °C °C
32
32
32
32
32
32
Volume flow rate combustion air
Nm
3
/h
404
467
525
583
671
759
Feed pressure
total at the combustion air/flue gas line
4
Pa
130
130
130
130
130
130
Maximum draught/depression at flue gas outlet
Pa
-50
-50
-50
-50
-50
-50
1
Data related to NCV.
The boiler series is tested for EE/H-settings. With a factory setting of the Wobbe coefficient
of 15.0 kWh/m
3
operation at a Wobbe coefficient of 12.0 up to 15.7 kWh/m
3
is possible without new settings.
2
Data related to NCV.
3
See also notes at “Engineering”.
4
Details for multi-boiler plants (cascade) with common flue gas line: see Hoval UltraGas
®
(250D-2000D).
18
4 217 215 / 00
TECHNICAL INFORMATION