Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Segment #8 Soak
Time
0044
068
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Time
or
Soak Setpoint
Value
Segment #10
Soak Time
0047
071
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
Ramp Time
or
Soak Setpoint
Value
Segment #9 Ramp 0045
069
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
0 to 999 (Degrees/Minute)
Segment #10
0046
070
FP
R/W
Within Setpoint Limits
Segment #11
0048
072
FP
R/W
99.59 (0-99 Hrs:0-59 Min)
0 to 999 (Degrees/Minute)
Segment #12
0049
073
FP
R/W
Within Setpoint Limits
Segment #12
Soak Time
004A 074
FP
R/W
99.59 (0-99 Hrs:0-59 Min)