Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex
Decimal
Input Algorithm 1
† Input source
selected via ID
205, 206, 207.
00CC 204
INT R/W
0 = None
1 = Weighted Average
(LSP) †
2 = Feedforward –
Summer †
3 = Feedforward –
Multiplier †
4 = Unused
5 = Summer (with ratio and
bias) †
6 = Input High Select (with
ratio and bias) †
7 = Input low Select (with
ratio and bias) †
8 = General Math A
(sq. rt., mult., div.) †
9 = General Math B
(sq. rt., mult.) †
10 = General Math C
(mult., div.) †
11 = General Math D
(mult.) †
12 = Carbon A
13 = Carbon B
14 = Carbon C
15 = Carbon D
16 = Carbon FCC
17 = Dewpoint
18 = Oxygen
Constant K
002D 045
FP
R/W
0.001 to 1000
Calc High
001F 031
FP
R/W
–999.0 to +9999
in Engineering Units
Calc Low
0020
–999.0 to +9999
in Engineering Units
032
FP
R/W
PV Range Low
0036
054
FP
RD
–999.0 to +9999
in Engineering Units
PV Range High
0037
055
FP
RD
–999.0 to +9999
in Engineering Units