Installation
Table 2-6 Universal Output Functionality and Restrictions
Function of Other Outputs
Output Algorithm
Type
Output 1/2
Option
Function of
Output 1/2
Output #3
Output #4
Auxiliary Output
Single Relay
Output 1
Alarm 2
Alarm 1
Not Needed
Current Output
INU
Output 1
Alarm 1
Not Needed
Time Simplex
Dual Relay
Output 1
Alarm 2
Alarm 1
Not Needed
Single Relay
Output 1
Output 2
Alarm 1
Not Needed
Current Output
INU
Output 2
Output 1
Not Needed
Time Duplex or
TPSC or Position
Proportional
Dual Relay
Outputs 1 and
2
Alarm 2
Alarm 1
Not Needed
Single Relay
INU
Alarm 2
Alarm 1
Output 1
Current Output
Output 1
Alarm 2
Alarm 1
Not Needed
Current Simplex
Dual Relay
INU
Alarm 2
Alarm 1
Output 1
Single Relay
INU
Alarm 2
Alarm 1
Outputs 1 and 2
Current Output
Outputs 1 and
2
Alarm 2
Alarm 1
Not Needed
Current Dup. 100%
Current = COOL
and HEAT
Dual Relay
INU
Alarm 2
Alarm 1
Outputs 1 and 2
Single Relay
N/A
N/A
N/A
N/A
Current Output
Output 1
Alarm 2
Alarm 1
Output 2
Current Duplex
50%
Current = HEAT
Aux Out = COOL
Dual Relay
N/A
N/A
N/A
N/A
Single Relay *
Output 1
Output 2
Alarm 1
Output 2
Current Output
Output 2
Output 2
Alarm 1
Not Needed
Current/Time
Current = COOL
Time = HEAT
Dual Relay *
Outputs 1 & 2
Alarm 2
Alarm 1
Output 2
Single Relay *
Output 1
Output 2
Alarm 1
Output 1
Current Output
Output 1
Output 2
Alarm 1
Not Needed
Time/Current
Time = COOL
Current = HEAT
Dual Relay *
Outputs 1 & 2
Alarm 2
Alarm 1
Output 1
TPSC = Three Position Step Control
N/A = Not Available – This output algorithm type cannot be performed with this Output 1/2
option.
INU = Installed, Not Used – The installed Output 1/2 option is not used for the configured
output algorithm type.
Not Needed = Auxiliary Output is Not Needed to provide the desired output algorithm and can
be used for another purpose. With the proper configuration, Auxiliary Output
could also be used as a substitute for the Current Output.
* To obtain this output algorithm type with these Output 1/2 Options: 1) Configure the
OUTALG selection as “TIME D”; 2) Configure Auxiliary Output for “OUTPUT” and; 3)
Scale the Auxiliary Output as necessary for the desired output algorithm type. For these
12/04
UDC3200 Universal Digital Controller Product Manual
23