Troubleshooting/Service
Procedure #5
Table 7-9 explains how to troubleshoot Current/Time or Time/Current Proportional
Output failure.
Table 7-9 Troubleshooting Current/Time or Time/Current Proportional
Output Failure
Step
What to do
How to do it
1
Make sure the controller is configured
for Time/Current or Current/Time
Proportional output.
Make Output Algorithm Set Up group function
prompt OUT ALG = TCUR or CURT.
Refer to
.
2
Check the field wiring.
Make sure the NO or NC contact wiring selection
is correct.
Refer to
for details.
3
Check the relay output.
Put the controller into Manual mode. Vary the
output above and below the present value.
Observe OUT1 indicator on the operator interface.
Listen for a click from the relay when the OUT1
indicator changes state.
4
Check the Current Proportional
Output.
Put the controller into Manual mode and change
the output from 0 % to 100 % (4-20 mA). Use a DC
milliammeter at the rear terminals to verify the
output.
5
Recalibrate the controller.
Refer to
Section 6 - Output Calibration
for details.
6
Change MCU and/or Current Output
boards.
Installation instructions supplied with new board.